Exchanger will not heat properly
-
Problem
Tank contents overheating.
-
Cause
Temperature control sensor below or too far from heat source.
Solution
Verify control/sensor operation and secure sensor above bottom of exchanger and near work or reinstall coil deeper in tank.
-
Cause
Valve stuck in open position.
Solution
Test valve operation and repair/replace as required.
-
Cause
Improperly sized trap causing excessive condensate and time lags in system
Solution
Verify proper trap size and type required for application and replace as required.
-
Cause
Defective or damaged temperature control sensor on thermostat.
Solution
Consult temperature control trouble-shooting information and repair or replace as required.
-
Cause
Temperature control probe mounted in air.
Solution
Verify control/sensor operation and secure sensor adjacent to coil.
-
Cause
Temperature control out of calibration.
Solution
Verify temperature control accuracy by placing known accurate thermometer in same location a control sensor and calibrate as required.
-
Cause
Heat exchanger too large for application.
Solution
Verify all heating requirements and replace exchanger as required.
-
-
Problem
Reduced output of coil. Any time reduced output of a coil is suspected, tests should be performed to measure the pressure and temperature of the incoming source and amount of condensate or temperature of output water.
-
Cause
Low steam pressure. (Any pressure below the design rating of the coil significantly reduces the rated output of the exchanger.)
Solution
Measure the available pressure and compare it to the rating on the tag. Check and compare your incoming pressure at the boiler vs. the pressure at the coil. If the difference exceeds 3 psi consider increasing the pipe size or adding insulation. Either add additional coils or replace the coil with a larger one to add more exchanger surface area to increase capacity.
-
Cause
Temperature control sensor not located properly in tank.
Solution
Place/secure sensor 1/3 of way down in solution (preferably within a thermal well).
-
Cause
Steam pressure too low for proper operation of standard pilot operated valve.
Solution
Increase steam pressure at the valve or install a direct acting or zero pressure differential valve in its place.
-
Cause
Coils plumbed in series. (This condition would cause each successive coil to produce less than the rated output while increasing the pressure drop and condensate on the system substantially.)
Solution
Reconnect coils in parallel to an appropriately sized header
-
Cause
Water hammer damage to internal baffles within grid style coils which allows flow to bypass portions of the exchanger.
Solution
Contact factory for repair install drip trap before steam valve and water hammer arresters in supply line.
-
Cause
Buildup on coil sheath.
Solution
Inspect and clean coils on a regular basis appropriate to the rate of buildup from the chemistry employed. Check application, as larger/more surface area may be required in most solutions that buildup quickly.
-
Cause
Improperly sized exchanger.
Solution
Verify heat requirements and replace exchanger as required.
-
Cause
Coil not fully submersed in fluid being heated.
Solution
Fill tank to submerse coil or correct mounting or plumbing to accommodate low fluid level.
-
Cause
Inlet/outlet connections reversed on steam coil.
Solution
Verify inlet/outlet per installation instructions and correct connections as required.
-
Cause
Low temperature feed water supply (for heating). Too high temperature feed water supply for cooling.
Solution
Verify temperature of feed water and correct as required.
-
Cause
Steam trap installed on inlet side of coil.
Solution
Reconnect stream trap on outlet side of coil.
-
Cause
Plugged vent hole on steam trap.
Solution
Clean any deposits from trap vent.
-
Cause
Blocked strainer.
Solution
Clean or replace strainer.
-
Cause
Undersized supply piping.
Solution
Calculate BTU requirements for tanks and respective flow requirements. Rework or replace coil inlet/outlet tubes to accommodate flow.
-
Cause
Steam coil operated on water service. Grid style water coils require baffles to direct internal flow. (Note: Coils designed for water service will operate fine in both steam or water applications.)
Solution
Replace coil with one designed for water service.
-
Cause
Back pressure from condensate return on low-pressure steam systems can prevent outflow of condensate from trap
Solution
Verify that pressure on condensate leg is below pressure on outlet of each individual coil.
-
Cause
Condensate return line and/or trap above exchanger.
Solution
Do not route condensate return above outlet of exchanger without condensate pump. Trap should be mounted 18" below coil outlet. Correct trap location and condensate piping as required.
-
Cause
Undersized supply piping.
Solution
Calculate BTU requirements for tanks and respective flow requirements. Rework or replace coil inlet/outlet tubes to accommodate flow.
-
Cause
Steam coil operated on water service. Grid style water coils require baffles to direct internal flow. (Note: Coils designed for water service will operate fine in both steam or water applications.)
Solution
Replace coil with one designed for water service.
-
Cause
Undersized supply piping.
Solution
Calculate BTU requirements for tanks and respective flow requirements. Rework or replace coil inlet/outlet tubes to accommodate flow.
-
Cause
Condensate return line and/or trap above exchanger.
Solution
Do not route condensate return above outlet of exchanger without condensate pump. Trap should be mounted 18" below coil outlet. Correct trap location and condensate piping as required.
-
Cause
Steam lock on piping between coil and trap.
Solution
Re-plumb trap 18" below exchanger outlet line with as short of horizontal pipe as possible. If problem persists, install steam lock release or trap with integral steam lock release.
-
Cause
Improperly sized trap.
Solution
Calculate BTU requirement for tank and verify proper trap sizing. Replace as required.
-
Cause
Multiple coils on single steam trap.
Solution
Each coil must have its own trap for proper operation. Verify operating parameters for each coil and install an appropriately sized trap.
-
Cause
Improperly sized solenoid valve.
Solution
Evaluate BTU requirement for tank and verify valve Cv rating. Replace valve as required.
-
Cause
Improper trap style selection.
Solution
Inverted bucket traps work fine on metal coils, however, balanced pressure or thermostatic traps perform better on fluoropolymer exchangers by reducing air binding. Replace traps as required on fluoropolymer coils.
-
Cause
Condensate return line and/or trap above exchanger.
Solution
Do not route condensate return above outlet of exchanger without condensate pump. Trap should be mounted 18" below coil outlet. Correct trap location and condensate piping as required.
-
Cause
Condensate line plumbed above exchanger causing back pressure on trap.
Solution
Re-plumb condensate return system or add condensate sump/pump to evacuate condensate.
-
Cause
Air-bound steam trap. Air in system both insulates and dilutes the steam reducing its temperature and forms a film on the exchanger walls limiting heat transfer.
Solution
Change trap style to one that can vent air from system faster or install a bypass bleed valve to evacuate air in line.
-
Cause
Unbalanced load/mixed types of coils.
Solution
Multiple coils should be plumbed to a single appropriately sized header and with valves provided to distribute/adjust each output. Combining water coils of different sizes, or non-uniform groupings will cause unbalanced pressure drops on one or more of the coils and inefficiencies.
-
Cause
Buildup inside exchanger sheath. Caused by particulates or colloidal materials that have accumulated on the coil interior surfaces from the water/steam source.
Solution
Dissolve away all deposits with exchanger with a chemically compatible cleaner. Install a water conditioner and strainer on the water/steam supply.
-
Cause
Viscous or concentrated solution. Dense or concentrated solutions impede heat flow from the sheath and can reduce performance.
Solution
Increased mixing of the solution near the coil can reduce the problem. Consider installing multiple coils and space them evenly around the tank to enhance heat distribution.
-
Cause
Kinked or damaged tubes.
Solution
Visually inspect all exchanger tube surfaces for dents, kinks or collapsed tubes. Repair or replace as required. Protect coil from damage with guards or move to protected location.
-
-
Problem
Valve not turning on
-
Cause
Solenoid valve electric operator coil open/burned out.
Solution
Test operator coil by applying rated voltage and replace coil or valve as required.
-
Cause
Solenoid valve stuck in closed position by deposits.
Solution
Clean/repair valve if possible. Install strainer on inlet supply prior to valve to reduce particulate matter flowing through valve.
-
Cause
Low pressure. (Many pilot operated solenoid valves require 5 PSIG minimum pressure drop across valve to operate.)
Solution
Increase pressure on supply or replace valve with a zero pressure drop model valve.
-
Cause
N/O solenoid valve used instead of N/C valve.
Solution
Verify valve operation and replace as required
-
-
Problem
Supply problems, no steam/hot water.
-
Cause
Steam/hot water source is blocked by shut off valves.
Solution
Verify that all valves preceding coil are open and supply is available to coil.
-
Cause
Plugged strainer.
Solution
Open and clean strainer.
-
Cause
Defective trap or mis-sized trap
Solution
Repair or replace trap.
-
Cause
Solenoid valve not connected to terminal blocks in control
Solution
Connect as required.
-
Cause
Solenoid coil voltage does not match power supply
Solution
Replace solenoid valve or coil to match available power.
-
Cause
Improper wiring/voltage not jumpered to isolated contacts of control.
Solution
Verify wiring with appropriate diagram and correct if necessary.
-
Cause
Incorrect thermostat settings.
Solution
Verify thermostat settings and switch operation, repair or replace as required.
-
Cause
Defective temperature control/sensor.
Solution
Verify temperature control operation, repair or replace as required.
-